Glass coating tests, with the conditions attached.

Review the supplied SGS reports, what each measurement means and what to confirm for your project.

Download the sample reports

These reports identify the sample as ‘Glass insulation coating/liquid thermal film’, not G801 or G802. Results apply to the submitted samples. Confirm model, formulation and batch applicability before specifying a product.

Optical performance

ReportSHIN2608002834CM02_EN
Issued2026-09-08
LaboratorySGS-CSTC Standards Technical Services (Shanghai) Co., Ltd.
Submitted sampleGlass insulation coating/liquid thermal film
Model identificationNot specified in the report
Test methodsISO 9050:2003; ASTM E903-20; JG/T 235-2014 Annex A; ASTM D1003-21 Procedure A

Physical properties

ReportSHMR260802229401
Issued2026-09-09
LaboratorySGS-CSTC Standards Technical Services (Shanghai) Co., Ltd.
Submitted sampleGlass insulation coating/liquid thermal film
Model identificationNot specified in the report
Test methodsISO 15184:2020; ISO 2409:2020; ISO 2808:2019

Reported sample results

MeasurementReported valueSpecimen and test conditions
Visible-light transmittance (VLT)76.77%Glass specimen 100 × 100 × 4.3 mm; 23.9°C, 48.6% RH. Dry-film thickness and coating cure age are not stated.
ISO 9050:2003, 3.3
SHIN2608002834CM02_EN
UV transmittance0.40%Glass specimen 100 × 100 × 4.3 mm; 23.9°C, 48.6% RH. Dry-film thickness and coating cure age are not stated.
ISO 9050:2003, 3.6
SHIN2608002834CM02_EN
Solar transmittance29.5%Glass specimen 100 × 100 × 4.3 mm; 23.9°C, 48.6% RH. Dry-film thickness and coating cure age are not stated.
ASTM E903-20
SHIN2608002834CM02_EN
Solar absorptance66.2%Glass specimen 100 × 100 × 4.3 mm; 23.9°C, 48.6% RH. Dry-film thickness and coating cure age are not stated.
ASTM E903-20
SHIN2608002834CM02_EN
Near-infrared transmittance5.45%Glass specimen 100 × 100 × 4.3 mm; 23.9°C, 48.6% RH. Dry-film thickness and coating cure age are not stated.
JG/T 235-2014 Annex A
SHIN2608002834CM02_EN
Haze0.5%Sample A; specimen thickness 4.4713 mm; illuminant C; pretreatment 40 h at (23 ± 2)°C and (50 ± 5)% RH. Coating cure age is not stated.
ASTM D1003-21 Procedure A
SHIN2608002834CM02_EN
Pencil hardness3HA — coated glass panels; pretreatment 16 h at (23 ± 2)°C and (50 ± 5)% RH. Coating cure age is not stated.
ISO 15184:2020
SHMR260802229401
Cross-cut adhesion0A — coated glass panels; pretreatment 16 h at (23 ± 2)°C and (50 ± 5)% RH. Coating cure age is not stated.
ISO 2409:2020
SHMR260802229401

The near-infrared method is outside the report’s CNAS accredited scope. Transmittance is not reflectance, TSER or SHGC. The physical and optical reports must not be combined to infer one specimen’s coating thickness or curing history.

Understand the four key measures

VLT

The share of visible light transmitted through the tested glazing. Compare only with the substrate and test conditions stated.

TSER

Total solar energy rejection describes solar energy kept outside by a glazing system. It is not the same as near-infrared rejection.

SHGC

Solar heat gain coefficient includes directly transmitted solar energy and the part of absorbed heat that flows indoors. Lower values indicate less solar heat gain under the stated conditions.

Haze

The proportion of transmitted light that is scattered. Review it alongside VLT and a visual trial to assess clarity.

From a laboratory panel to your building

Glass construction, coating thickness, cure age, orientation, weather and ventilation affect the result. Record these conditions for a side-by-side trial. The supplied reports do not establish a model-specific SHGC, TSER, energy-saving percentage, room-temperature reduction or service life.

Questions about the results

Why can coated glass look darker?

A coating changes the light transmitted through the glazing. Compare a trial panel on the actual glass in daylight and at night before approving the finish.

Will a coastal site have the same service life?

Salt exposure, humidity, cleaning and surface condition can affect a coating. Agree site-specific preparation, maintenance and warranty terms; these reports are not a coastal durability test.

Can the coating replace air conditioning?

No such replacement is promised. Solar control is one part of a building’s heat balance; occupancy, ventilation, insulation and climate also matter.

From a sample to a supply plan

We welcome enquiries from glazing contractors, window and sunroom businesses, renovation companies, property owners and overseas partners.